11. COMMUNICATION
11.1 C-Ring : communication between controllers (for detailed information please see technical data sheet T 022)
RTR 684 controller can be “Primary” or “Secondary”.
In C-Ring the following signals are transmitted :
– permission to operate as Slave controllers
– value of the outside temperature (use of a single detector for several controllers)
– value of flow temperature requested by controllers heating zones, used by “PRIMARY”
controller for control of temperature boilers (if scheduled).
DHW priority and / or anticondensing = closure valves heating zones by modulating control
action.
NO = connection to C-Ring not scheduled
PRIMARY = connected to C-Ring and configured as “Primary”
SECONDARY = connected to C-Ring and configured as “Secondary”
11.2 C-Ring wiring diagram
24.2
CR i ng connec t i on
NO
12. OPERATION
RTR 684 is a digital controller with microprocessor which can control temperature in two zones each
with independent settings and programmes of timed events :
• Primary control
• Auxiliary control
It is indispensable to configure the controller according to the detectors and controls connected.
13. PRIMARY CONTROL
RTR 684 can operate with two different and independent measurement ranges :
• 0…99 °C (hot water) : detector B1, terminals B1-M
• 0…40 °C (cold water or ambient) : detector B3, terminals B3-M
Note It is not possible to configure both the detectors (B1 and B3).
RTR 684 can control by two different systems :
• With only the primary detector (B1 or B3)
• With the primary detector (B1 or B3) and the flow detector (B2)
13.1 Control with primary detector only (B1 or B3)
RTR 684 compares desired temp. T
°d from current programme chosen in
with temperature measured by detector B1 or B3 and adopts control action Y1 or
E1 according to temperature difference and parameters set :
if
Prop Band : – – . – c
= proportional band Pb in ± °C
Integ time : – – m
= integral time in minutes
if
Diff : – – . – c
= On-Off diferential of stage t°
Integ time : – – m
= integral time in minutes
Con f i g de t ec t o r s
1–––––
24.1
Prop band : 10 . 0c
Integ time: 10m
22.3
Con t r o l :
MODULATI NG
22.1
Con t ro l :
ON- OFF D I FF
22.1
Di f f :10.0c
Integ time: 10m
22.5
Con f i g de t ec t o r s
1–
24.1
Con f i g de t ec t o r s
–3
24.1
Pri:------------
2 4HOUR 1 PR I MARY
19.2
U
E
U
E
U
E
D D D
Primary
Secondary
or Slave
Secondary
or Slave
T
T
outside
detector
DHW
detector
t°
Pb
Y1
100%
0%
+
T°
d
Db
50%
t°
t°
E1
off
+
T°
d
t°
off
on
on
E1.2
E1.1